Power Management System


PowerSys-10

powersys-frontPowerSys-10 is an ideal product to control power source status the equipment through Global System of Mobile Communication (GSM Communication).

PowerSys-10 has been designed and manufactured using state-of-the-art technologies in order to deliver maximum protection for critical users, a zero impact on the mains power supply and a high operating efficiency.

 

Technical Specifications:

» 2U Rack mount platform
» CPU 32bit industrial multifunction
» AMD Geode LX800 Processor, Speed 500MHz
» RAM 256MB expandable up to 1GB
» Storage 1GB expandable up to 4GB
» LCD display and Status LED
» Operating humidity 0oC – 60oC
» Power Supply +12V
» Voltage 220V + 8%
» Input frequency range 47Hz – 52Hz
» Protocol with TCP/IP
» Supported for 10 clients

Features
» Detection for power source status
» Soft shutdown for client
» Auto turn off for client via GSM Communication
» Remote command, monitoring, and report via GSM Communication

Pro Power One

power1A new breakthrough in the management of electricity resources, Power Management System allows you to manage power from a multi-source.

Equipped with remote applications feature via short message services, access control and information about the status of electric power can be observed easily.

Technical Specifications:

Features
Equipment that is designed with 19” rack mounted platform is equipped with excellent features include:
» Bank power
» BCR (Battery Charge Regulator) with variable input voltage, 12 Volt, 24 Volt and 48 Volt, optional input from Solar panel
» Sensor for : temperature, humidity, storage battery, electricity (main power)
» UVD/ LVD (Upper/ Lower Voltage Disconnection)
» Controlling for power plan with  auto shutdown, auto turn on, or auto sleep
» Communication by Ethernet, RS232 for management
» SMS server monitoring
» Solid state controller : step-up or step-down
» Power by-pass or auto chargingControl power features
» Auto sleep for battery power 40%-20%
» Auto shutdown for battery power 19%-15%Input
» VDC = 12, 24, 48
» VAC = 90-240
» Solar cell (Optional)Output
» VDC = 12, 24, 48 (Optional)
» VAC = 220 sinus

AC Input
» AC input range : (182~240) + 5 Vac
» Frequency range : (45~55) + 0.5 Hz

DC Input
» Rated current (A) : 21
» Rated voltage (VDC) : 48
» Start input max impact current : less than 150% rated current
» DC input range of normal start : (40~60) + 1VDC

AC Output
» AC output (VAC) : 220 or 230V + 3% (inverter output)
» Rate output capacity : 1000VA/ 700W
» Frequency (Hz) : 50+2Hz (AC input is normal), 50Hz+10% (AC input is abnormal)
» Power factor : 0.7
» Wave form : sine wave, THD<3% (linear load), sine wave, THD<8% (nonlinear load)
» Back up time : depend on battery capacity, default is 30 minutes

Others
» Display : TFT LCD, LED
» Alarm Function : sync input is abnormal, DC input is abnormal, overload, inverter Failure
» Protection Function : DC input under voltage or over voltage, overload, short-circuit, output over voltage or under voltage,over temperature
» Communication function : DB9, RJ45 communication port (contain one RS232 and dry contactor communication signals)
» Working temperature (oC) : -10~40
» Relative humidity : 0~95% (without condensation)
» Noise (dB) : < 55 (1m distant)
» Inverter storage temperature (oC) : -40oC~65oC
» Storage environment : relative humidity 0~95% (without condensation)
» Dimension : 19″ Close Rack 12U (H x W x D = 600 x 600 x 800mm)
» Weight (kg) : 20kg excluded battery

Pro Power 2

power2Pro Power 2 is ideal for the protection of critical information and telecommunications networks which cannot run the risk of being powered from a power quality electrical supply.

Pro Power 2 has been designed and manufactured using state-of-the-art technologies in order to deliver maximum protection for critical users, a zero impact on the mains power supply and a high operating efficiency.

Features
» Platform Rack Mount 19″
» UPS Capacity 20kVA

 

 

Technical Specifications

Input
» Rate Voltage : 380-400-415 VAC Three-Phase with Neutral
» Rated Frequency : 50/60 Hz
» Frequency Tolerance : min 40 ÷ 72 Hz
» Power Output at Full Load: 0,99 Pf / 95 Pf
» Current Distortion THDI < 3%

By Pass
» Rate Voltage : 380-400-415 VAC Three-Phase with Neutral
» Number of phases : 3+N
» Voltage Tolerance : 180 ÷ 264 V
» Frequency Tolerance : ± 5 (selectable)

Output
» Rated Power : 20kVa
» Active Power min 18 KW
» Output Power Factor min 0.9
» Number of phases: 3+N
» Rated Voltage : 380-400-415 VAC (selectable)
» Static Variation : ±1%
» Dynamic Variation : ±3%
» Crest Factor : (lpeak/lrms): 3:1
» Voltage Distortion : ≤1% with Linear Load /  ≤3% with non-linear load
» Frequency : 50/60 Hz
» Frequency Stability on BATTERY mode min 0.01%
» Overload at pF 0.8: 115% Unlimited, 125% for 10 minutes, 150% for 1 minute, 168% for 5 seconds

datasheet

Battery
» Recharge Time : max 6h
» Protection Rating : IP 20

Communication, Display, and Network
» Compatible with TeleNetGuard for The Remote Assistance Service
» 3 Slots for The Installation of Optional Communication Accessories such as Network Adapters and Volt-Free Contacts
» Remote Emergency Power Off with Switch to Power Down the UPS Through a Remote Emergency Pushbutton
» Graphic Mimic Panel Display for Remote Connection

Sensor & Control
» Temperature Sensor for External Battery Cabinets and Alert for Over Heater Environments
» Sensor Alert for Main Power Off or Main Power Up
» Auto Sleep and Turn Off / Shutdown for Connected Product to UPS If Battery Reach LVD
» Alert Info via Short Message Service